Remote
display can be mounted in 1/8 DIN panel cutout or on surface mount
bail
|
COMMON
SPECIFICATIONS
Accuracy:
▒0.005% rdg
Span Temperature Coefficient: ▒20 ppm
Step Response: 1 sec to 99.9%
Warmup to Rated Accuracy: 50 min
Operating Ambient: 0 to 50░C, 95%RH, non-condensing
Storage Ambient: -40 to 85░C
Power: 230 Vac, 49-400 Hz; 10 to 32 Vdc
Power Consumption: 6 W nominal, 10 W max
Normal Mode Rejection: 60 dB
Common Mode Rejection: 120 dB
Common Mode Voltage: 1500 V peak per HV test
Resolution: 15-bit
Conversion: dual-slope technique
Reading Rate: 3/sec or 13/sec, 60 Hz; 3/sec or 12/sec, 50 Hz
Display: red or green 6-digit, 14-segment, 13.7 mm (0.54"); 4 alarm
indicators
Dimensions: 48 H x 96 W x 165 mm D (1.9" x 3.8" x 6.5")
Panel Cutout: 45 H x 92 mm W (1.8" x 3.6"); 1/8 DIN
Weight: 574 g (1.27 lb)
TTL Outputs: four, isolated open collector; rated 150 mA at 1 V
sink, 30 V open
BCD Output: isolated, tri-state, TTL/CMOS compatible; external
5 V supply for isolated; internal 5 V supply for non-isolated
Dual Relays: form C, 7 A at 30 Vdc or 230 Vac
Four Relay Option: dual 7 A relays and dual 1 A relays
Analog Output
0-5 V/1-5 V/0-10 V/ 0-20 mA/4-20 mA, user selectable; 354 Vp isolation;
15-bit resolution; 0.1% accuracy, 50 msec step response
RS-232 Communications
300/600/1200/2400/4800/9600/19.2k baud; RJ11 4-wire connection; complete
program setup and message display capability; programmable to transmit
current display, alarm status, min/max, actual measured input value and
status
RS-485 Communications
300/600/1200/2400/4800/9600/19.2k baud; RJ12 6-wire connection; addressable
from 0 to 199
PROCESS INPUTSùINFXU, INFXP, INFXS, INFXW
Voltage Input Ranges: 0-100 mV, 0-1 V, 0-5 V, 1-5 V, 0-10 V, 0-100
V, ▒50 mV, ▒500 mV, ▒5 V, ▒50 V
Current Input Ranges: 0-20 mA, 4-20 mA
Input Configuration: single-ended
Polarity: Unipolar/bipolar, programmable
Span Adjustment: 0.00001 to 500,000; programmable
Offset Adjustment: 0 to 999,999 or 0 to -99,999; programmable
TEMPERATURE INPUTSùINFXU, INFXT
Thermocouple Input Types: J, K, T, E, R, S, B, N, J DIN
RTD Input: any 6 to 6k ohm NIST or DIN platinum and any linear
RTD
RTD Connection: 2, 3 or 4 wire
Sensor Break Protection: upscale or downscale, programmable
Overvoltage Protection: 25 V peak
SENSOR EXCITATIONùINFXP, INFXS, INFXU, INFXW
Sensor Excitation, INFXS, INFXU, INFXW: 10 V to 30 mA; 24 V to
25 mA Sensor Excitation, INFXP: 24 V to 25 mA
Models - INFXU, INFXP, INFXS, INFXW, INFZU, INFZP, INFZS, INFZW |
|
Models - INFXU, INFXT, INFZU, INFZT |
Range Code
|
Range
|
|
Range Code
|
Range
|
DC1
|
0-100 mV
|
|
J (*)
|
J Iron-Constantan
|
DC2
|
0-1 V
|
|
K (*)
|
K CHROMEGA
-ALOMEGA
|
DC3
|
0-5 V
|
|
E (*)
|
E CHROMEGA
-Constantan
|
DC4
|
1-5 V
|
|
T (*)
|
T Copper-Constantan
|
DC5
|
0-10 V
|
|
B (*)
|
B Pt30%Rh-Pt6%Rh
|
DC6
|
0-100 V
|
|
R (*)
|
R Pt13%Rh-Pt
|
DC7
|
▒50 mV
|
|
S (*)
|
S Pt10%Rh-Pt
|
DC8
|
▒500 mV
|
|
N (*)
|
N Nicrosil-Nisil
|
DC9
|
▒5 V
|
|
J DIN (*)
|
J DIN
Iron-Constantan
|
DC10
|
▒50 V
|
|
RTD1 (*)
|
RTD 10 ohm
Copper
|
C1
|
0-20 mA
|
|
RTD2 (*)
|
RTD 100 ohmPt
0.00385
|
C2
|
4-20 mA
|
|
RTD (*)
|
RTD 100 ohm
Pt 0.00392
|
*
Specify C (Celsius),
F (Fahrenheit) or K
(Kelvin) |